Models |
Nxa |
Rated Power @ 0.8 PF [kVA] |
40Kva |
Rectifier Input |
|
Rectifier Type |
IGBT-based Vector Controlled PFC (PF Corrected) |
Input Voltage [Vac] |
380 / 400 / 415 (Accepted from 305 to 477 without batt. Use) |
Input Frequency [Hz] |
50 or 60 (Accepted range from 40 to 70) |
Input Current |
THD <3% (without any Filter) |
Input Power Factor |
≥ 0.99 (without any Filter) |
Power Walk-In [s] |
5 to 30 (selectable) |
Bypass Input |
|
Input Voltage [Vac] |
|
Battery |
|
Battery Type |
VRLA (Valve Regulated Lead Acid) or Wet / Flooded or NiCd |
End-Cell Voltage [Vdc/Cell] |
Selectable from 1.60 to 1.90 (for VRLA) |
DC Ripple Current (float) |
<5% (of C10 AH capacity) RMS value |
DC Ripple Voltage |
<1% (RMS value) |
Temp. Comp. Charge |
Standard (where internal batteries 10, 15, 20, 30, 40 kVA) |
Output |
|
Inverter Type |
IGBT-based Vector, Repetitive & PI Controlled |
Output Power [kW] |
32Kw |
Output Voltage [Vac] |
380 / 400 / 415 +/- 0.5 Regulation (3-phase RMS average) |
Output Frequency [Hz] |
50 or 60 with +/- 0.05 Regulation |
Output Voltage THD |
1% (max) |
Max. Load Crest Factor |
3:1 (compliant with IEC 62040-3) |
Transient Volt. Resp. [ms] |
10 to recover ± 5% of Nominal Voltage for 0% to 100% or 100% to 0% step load |
Max. Leading PF Load |
Up to 0.9 |
Voltage Displacement [°el] |
120°+/-10 el (with 100% unbalanced load) |
Overload |
110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute |
Efficiency |
|
AC-AC |
Up to 96 |
Physical Parameters |
|
Width [mm] |
600 |
Depth [mm] |
825 |
Height [mm] |
1600 |
Weight (approx.) |
|
without batt. [kg] |
341 |
UPS Enclosure IP |
IP 20 (even with open front door) |
Standards |
IEC 62040-3, IEC 62040-2, IEC 62040-1-1, IEC 60146-1-1, |
EMC Class |
Class-A (Applicable for both Radiated & Conducted) |
Environmental |
|
Storage Temp. [°C] |
*-20 to 70 (UPS) & -20 to 30 (Battery) |
Operating Temp. [°C] |
0 to 40 (UPS) & 25 +/-5 (Battery) |
Relative Humidity |
0 to 95% (non-condensing) |
Maximum Altitude [m] |
1000 (as per IEC 62040/3) |