Output |
|
|
Output Power Capacity |
16 kW / 20 kVA |
|
Max Configurable Power |
16 kW / 20 kVA |
|
Nominal Output Voltage |
230V |
|
Output Voltage Note |
Configurable for 220 : 230 or 240 nominal output voltage |
|
Output Frequency (sync to mains) |
50/60 Hz +/- 3 Hz user adjustable +/- 0.1 |
|
Efficiency at Full Load |
94% |
|
Output Voltage Distortion |
Less than 3% at full load |
|
Crest Factor |
3 : 1 |
|
Waveform Type |
Sine wave |
|
Output Connections |
(1) Hard Wire 3-wire (H N + G) (1) Hard Wire 5-wire (3PH + N + G) (8) IEC 320 C19 (2) IEC Jumpers |
|
Overload Operation |
60 seconds @ 125% and 30 seconds @ 150% |
|
Bypass |
Built-in Static Bypass,Internal Bypass (Automatic and Manual),Optional External Bypass |
|
Input |
|
|
Nominal Input Voltage |
230V, 400V 3PH |
|
Input Frequency |
40 - 70 Hz (auto sensing) ) |
|
Input Connections |
Hard Wire 3 wire (1PH+N+G) Hard Wire 5-wire (3PH + N + G) |
|
Input voltage range for main operations |
160 – 280V |
|
Input voltage adjustable range for mains operation |
160 – 280V |
|
Other Input Voltages |
220,240 |
|
Maximum Input Current |
115A |
|
Input Breaker Capacity |
125. 0 A |
|
Input Total Harmonic Distortion |
Less than 5% for full load |
|
Batteries & Runtime |
|
|
Battery Type |
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
|
Included Battery Modules |
4 |
|
Typical recharge time |
2.50 hour(s) |
|
Replacement Battery |
RBC44 |
|
RBC™ Quantity |
4 |
|
Nominal Battery Voltage |
+/-192 V (split battery referenced to neutral) |
|
End of Discharge Battery Voltage |
+/-154 V |
|
Efficiency in Battery Operation |
93% |
|
Extended Run Options |
|
|
Communications & Management |
|
|
Interface Port(s) |
DB-9 RS-232,RJ-45 10/100 Base-T,Smart-Slot |
|
Pre-Installed SmartSlot™ Cards |
AP9631 |
|
Control panel |
Multi-function LCD status and control console |
|
Audible Alarm |
Audible and visible alarms : configurable delays |
|
Emergency Power Off (EPO) |
Yes |
|
Surge Protection and Filtering |
|
|
Filtering |
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 |
|
Physical |
|
|
Maximum Height |
533.00 mm |
|
Maximum Width |
432.00 mm |
|
Maximum Depth |
773.00 mm |
|
Rack Height |
12U |
|
Net Weight |
247.73 |
|
Shipping Weight |
314.27 KG |
|
Shipping Height |
990.00 mm |
|
Shipping Width |
610.00 mm |
|
Shipping Depth |
1003.00 mm |
|
Color |
Black |
|
Units per Pallet |
1: 00 |
|
Environmental |
|
|
Operating Environment |
0 - 40 °C |
|
Operating Relative Humidity |
0 – 95% |
|
Operating Elevation |
0-3000 meters |
|
Storage Temperature |
-15 – 45 °C |
|
Storage Relative Humidity |
0 – 95% |
|
Storage Elevation |
0-15000 meters |
|
Audible noise at 1 meter from surface of unit |
55.00 dBA |
|
Online Thermal Dissipation |
2800.00 BTU/hr |
|
Conformance |
|
|
Regulatory Approvals |
BSMI,EN/IEC 62040-2,EN/IEC 62040-1-1,VDE |
|
Standard Warranty |
2 years repair or replace |